Permit: T07CM01080

Parcel: 11502178C


Addresses:

505 E LEE ST

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
06/20/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
06/15/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) H2.5 CONNECTION AT 2 X 10 JOIST AT PATIO TO EXT WALL NOT PER PLAN CONNECTION NEEDS TO BE ON 2 X 10 NOT TJI 11/A-7
2) NAILING ON KINK STUD AT HOLDOWN NEEDS TO BE 2 X STUDS
3) MISSING ST1 AT 2ND FLOOR OPENING
4) 2 X 6 BLOCKING FOR PARALELL BLOCKING 2ND FLOOR WALLS TO FLOOR JOIST
5) EXT. WALLS MISSING H.25 PER 9/A-7
6) MISSING WEB STIFFNERS PER 6/A-7
05/15/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ST1 INSTALL INCOMPLETE
2) PORCHES NOT FRAMED
3) EXCESSIVELY SPAULED HOLDOWNS TO BE EPOXIED APPROVED RETRO FITS INSTALLED AND SPECIAL INSPECTED
4) STOPPED INSPECTION
5) COMPLETE AND RECALL
05/11/2007 EXT METAL CLIPS/EXT SHEATHING Cancelled IVRS - RI canceled