Permit: T07CM01074

Parcel: 11901065B


Addresses:

3301 S 6TH AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/24/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
OK FOR FINAL
TESTED DUCT SMOKE DETECTORS
AIR BALANCE OK
04/21/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COMPLETE SEALANT ON ROOF
2. PROVIDE AUDIO AND VISUAL ALARM FOR DUCT DETECTOR
3. PROVIDE DUCT SMOKE DETECTOR TEST
04/20/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. SEAL LINE SET PENETRATIONS AND PROVIDE U.V RESISITANT COATING OVER EXPANDABLE FOAM SEALANT.
2. PROVIDE AIR BALANCE REPORT.
3. RESTROOM E.F. COVER MISSING
4. T-STATS NOT PROPERLY INSTALLED