Permit: T07CM01074

Parcel: 11901065B


Addresses:

3301 S 6TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/23/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK FINAL
04/22/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. FINISH ROOF
2. FINISH SWITCHBOARD AND LABELING
3. FINISH EM/EXIT LIGHTING

RECEIVED CHECK#1689 -- $150.00
04/21/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
ROOF:
1. TIGHTEN LOOSE FITTINGS
2. MAINTAIN WORKING CLEARANCE 110.26
3. PLEASE VERIFY IF 440.14 APPLIES TO REFRIGERATION COMPRESSORS

STORE:
1. FINISH PREVIOUS ITEMS
2. FINISH SWITCH BOARDS
04/20/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. EM/EXIT LIGHT TO BE AS PER PLANS AND 700.12(F)
2. SEAL WALK-IN BOXES AS PER 300.7
3. STRANDED CONDUCTORS NOT SEATED WELL UNDER SCREW TERMINALS
4. OUTSIDE FLUORESCENTS NEED DISCONNECTING
MEANS 410.73(G) ALSO, ABOVE WALK-INS

FINISH: WALK IN MAKE UP
FLOOR BOX
ROOF
PANEL AND SEALS
EM LIGHTS CHECK
04/17/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*