Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM01074
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/23/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL |
|
| 04/22/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH ROOF 2. FINISH SWITCHBOARD AND LABELING 3. FINISH EM/EXIT LIGHTING RECEIVED CHECK#1689 -- $150.00 |
|
| 04/21/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ROOF: 1. TIGHTEN LOOSE FITTINGS 2. MAINTAIN WORKING CLEARANCE 110.26 3. PLEASE VERIFY IF 440.14 APPLIES TO REFRIGERATION COMPRESSORS STORE: 1. FINISH PREVIOUS ITEMS 2. FINISH SWITCH BOARDS |
|
| 04/20/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. EM/EXIT LIGHT TO BE AS PER PLANS AND 700.12(F) 2. SEAL WALK-IN BOXES AS PER 300.7 3. STRANDED CONDUCTORS NOT SEATED WELL UNDER SCREW TERMINALS 4. OUTSIDE FLUORESCENTS NEED DISCONNECTING MEANS 410.73(G) ALSO, ABOVE WALK-INS FINISH: WALK IN MAKE UP FLOOR BOX ROOF PANEL AND SEALS EM LIGHTS CHECK |
|
| 04/17/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |