Permit: T07CM01074

Parcel: 11901065B


Addresses:

3301 S 6TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/23/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/17/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK OFFICE CEILING ELECTRIC
1. FLUORESCENT FIXTURES TO HAVE DISCONNECTING MEANS PER 410.73(G)
2. SEAL INTERNAL RACEWAYS FOR WALK-IN BOXES 300.7
04/06/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
*MAIN SWITCHGEAR IS BEING MODIFIED IN FIELD WILL NEED NRTL RE-EVALUATION

REVIEWED JOB WITH CONTRACTORS

1. PLEASE VERIFY BOX FILL
2. FILL UNUSED CONDUITS ABOVE SWITCHBOARD
3. 408.3 FOR SWITCHBOARDS - ENTER SECTION SERVED FOR CONDUCTORS
03/16/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
FOUNTAIN WALL OK
03/05/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS AND HARD LIDS EXCEPT FOUNTAIN WALL
03/02/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
02/27/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK SOFFITS MNGRS. OFFICE, CASH WRAP
OK WALLS EXCEPT FOUNTAIN AND MECH. ROOM
02/26/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
02/25/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS AT COFFEE BAR, RESTROOM, HALLWAY WEST EXT. WINDOW WALL, CAN LTG. OVER COFFEE BAR
02/23/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK OUTSIDE SOFFITS ROUGH
02/20/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
02/17/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL AT WALK IN COOLER