Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM01074
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/23/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/17/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK OFFICE CEILING ELECTRIC 1. FLUORESCENT FIXTURES TO HAVE DISCONNECTING MEANS PER 410.73(G) 2. SEAL INTERNAL RACEWAYS FOR WALK-IN BOXES 300.7 |
|
| 04/06/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* *MAIN SWITCHGEAR IS BEING MODIFIED IN FIELD WILL NEED NRTL RE-EVALUATION REVIEWED JOB WITH CONTRACTORS 1. PLEASE VERIFY BOX FILL 2. FILL UNUSED CONDUITS ABOVE SWITCHBOARD 3. 408.3 FOR SWITCHBOARDS - ENTER SECTION SERVED FOR CONDUCTORS |
|
| 03/16/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* FOUNTAIN WALL OK |
|
| 03/05/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS AND HARD LIDS EXCEPT FOUNTAIN WALL |
|
| 03/02/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 02/27/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK SOFFITS MNGRS. OFFICE, CASH WRAP OK WALLS EXCEPT FOUNTAIN AND MECH. ROOM |
|
| 02/26/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 02/25/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS AT COFFEE BAR, RESTROOM, HALLWAY WEST EXT. WINDOW WALL, CAN LTG. OVER COFFEE BAR |
|
| 02/23/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK OUTSIDE SOFFITS ROUGH |
|
| 02/20/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 02/17/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL AT WALK IN COOLER |