Permit: T07CM01067

Parcel: 133146610

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/08/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
12/04/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
SUPPORT MV VALVE AT WH
DRIP ON UNION AT RPA
CAULK DFS
12/01/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CALL FOR AND HAVE APPROVED ALL REQUIRED INSPECTIONS PRIOR TO FINAL. REVIEW INSP. HISTORY FOR LOOSE ENDS AND COMPLETE WORK.
11/28/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. NEED TO SEE RP CONN TO PIPING.
2. UNWRAP PIPING TO CHECK MATERIAL TYPE.
3. RP REQUIRES UNIONS.
4. PROVIDE APPROVED PLAN REVISIONS
5. PROVIDE CLEARANCE REQUIRED FOR PEX AT WH
18" - 604.11.2
6. PROVIDE TEMPERING OF HW PER UPC 414.1
7. PROVIDE STERILIZATION AND PAPER WORK PER UPC 609.9
8. CAULK FIXTURES
9. LOCATE CO AT SINK
10. CORRECT CRITICAL LEVEL ON URINAL FLUSH-O-METER
11. PROTECT PLASTIC VTRS
12. PROVIDE A SEPARATE SOV FOR DW