Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM01020
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/05/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
08/17/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PLEASE LEAVE OUT TILE AT FA DEVICES |
|
08/16/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - MISSED ONE 2X4 GRID LIGHT FOR SCREW TO GRID - COMPLETE FA |
|
08/14/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CHECK BOXES FOR OVERFILL 45 - X 1 1/4 = 8 #12 45 - X 1 1/2 = 9 #12 45 X 2 1/8 = 13 #12 2. LIGHT FIXTURES TO BE SECURELY FASTENED TO GRID CLIPS ON FIXTURES (2X4) LAY IN NOT EFFECTIVE - USE 2 SCREWS EA. FIXTURE 3. MOVE J-BOXES ABOVE SPRINKLER LINES FOR ACCESSIBILITY NEC/ARTS 110 410 413 |
|
08/09/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK HARD LIDS |