Permit: T07CM01016

Parcel: 10702002A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/17/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. FEEDERS COVERED BEFORE APPROVAL?
2. #6 EQUIPMENT GROUND TO BE GREEN ENTIRE LENGTH
NEC 250.119
3. PROPERLY TERMINATE GROUNDS IN PANELS -- DON'T STACK LUGS, SHEET METAL SCREW NOT ALLOWED FOR MOUNTING GROUND BAR, GROUND NOT TO BE WITH NEUTRALS.
4. IDENTIFY PANEL DIRECTORY - NEC 408.4