Permit: T07CM01012

Parcel: 11505087C


Addresses:

310 W SAHUARO ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM01012

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/03/2009 ELECTRIC - FINAL Approved
03/31/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK FOR TCO, SUBJECT TO OTHER INSPECTORS APPROVAL
2. FINISH UNIT HTRS. HOOKUP
03/25/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. EXIT LIGHTS TO BE AS PER 700.12 (F)
2. FINISH ELECTRIC

*PLEASE VERIFY LISTING OF PUMP FOR COOLER SYSTEM
03/09/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. BOND POLE BASES PER 250.53
2. BOND MAIN DISCONNECT ENCLOSURE

OK TEMP POWER FOR TEST (TMPP)