Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
Permit Number - T07CM01012
Inspection Description - ELECTRIC - TEMP POWER FOR TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/03/2009 | ELECTRIC - TEMP POWER FOR TEST | Approved | ||
03/09/2009 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* | |
09/04/2008 | ELECTRIC - TEMP POWER FOR TEST | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. GROUNDING ELECTRODE SYSTEMS TO BE AS PER 250.50 & 64 2. FINISH PREVIOUS ITEMS 3. TEMP POWER FOR TEST IS FOR FINISHED BUILDINGS ADD TEMP CONST. POWER |
|
09/02/2008 | ELECTRIC - TEMP POWER FOR TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. (2) GROUND RODS REQUIRED 6' MIN. APART 2. GROUND MODULAR WITH GROUND ELECTRODE #4 ALSO 3. MODULAR OFFICE SHOULD BE ON PERMIT DESCRIPTION AND TEMP. CONST. POWER |