Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM01012
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/03/2009 | ELECTRIC - INTERMEDIATE | Approved | ||
02/11/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO ROCK OK 4/0 TO 2 GROUNDING RECEIVED LETTER FOR GROUND RODS |
|
02/09/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* JUNCTION BOXES TO BE ACCESSIBLE T-STAT CABLES EAST WALL |
|
02/06/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROTECT VDV CABLING AT STUD FROM SHARP METAL EDGES 2. SUPPORT VDV CABLING 725.24 3. TIGHTEN LOOSE FITTINGS 4. REMOVE ABANDONED CABLING 5. FINISH DOOR HEADER OK TO ONE SIDE |
|
02/05/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. NO MORE THAN 360 DEG. IN CONDUIT RUNS 2. SUPPORT CONDUIT AS PER CODES 3. TIGHTEN LOOSE FITTINGS 4. PROTECT END OF CONDUIT FOR VDV 5. SUPPORT MC WITHIN 12" OF CANS AND EXHAUST FANS 6. CANNOT USE 3/8 FLEX 348.20 NO ROCK YET |
|
01/09/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* OK TIN CEILING SOUTH 1/2 1. WHERE ARE INSPECTION REPORTS FOR CONDUIT & BOXES IN BLOCK WALLS |