Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
05/03/2007 FRAMING Approved IVRS - Inspection :*
05/02/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLETE #1
2) NO WATER ON A.B.'S
04/30/2007 FRAMING Not ready for Inspection IVRS - Inspection :*
1) COMPLETE ITEMS 1, 2, 6, 7 & 8 FROM PRIOR INSPECTION
2) KITCHEN EXHAUST REMOVED
3) SOME ELECTRIC BOXES REMOVED FOR H.D.'S, SOME WIRE MISSING UPSTAIRS
4) STOPPED INSPECTION
04/26/2007 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) SHEARWALL 9 REQUIRES 3 INCH NOMINAL MEMBERS AT PLATE AND ENDS PER NOTE 6/A2.2
2) HOLDOWNS ANCHOR BOLTS NOT INSTALLED
3) TRIPPLE 2 X POSTS FROM GIRDER TRUSS MUST EXTEND TO FOUNDATION
4) BEARING STUD BY RANGE HOOD CUT. REPLACE WITH FULL STUD NAILTO SHEARWALL
5) TWO ANCHOR BOLTS REQUIRED IN SILL PLATES AND WITHIN 12" OF ENDS
6) SHEAR BLOCKING MISSING BROKEN BY ENTRY. NAIL TO SHEAR
7) STAIR SHEAR WALL STRAPS IN WRONG LOCATIONS MUST GO ON ENDS ABOVE HOLDOWNS
8) BLOCK ALL SHEARWALL EDGES AND NAIL TO SHEAR
9) STOPPED INSPECTION-BUILD TO PLAN