Permit: T07CM01007

Parcel: 141315020

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T07CM01007

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
04/24/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
04/19/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REAR PORCH HIP TRUSSES REQUIRED HANGERS
2) PORCH HIP JACKS TIE TO BEAMS WITH H2.5
3) NEED MORE 1/2" A.B. AND H2.5 STUDS TO PLATE
4) 1ST/2ND FLOOR STRAPS NOT NAILED
5) NAIL ALL WIND BRACES, 2 NAISL IN EACH PLATE END
6) 36" STRAP HORIZONTAL ACROSS GARAGE BEAM TO SHEAR CS 20 X 36"
7) FRONT 2ND FLOOR SHEAR CUT FOR OVER HANG ? BLK AND NAIL, FILL IN WITH OSB
8) MISSING REAR SHEAR NAILING 2ND FLOOR
9) 3-4' AREAS MISSED ON ROOF 2 REAR ONE FRONT REAR MAKED ON ROOF IN BLACK, FRONT MARKED ON FLOOR BELOW
10) FRONT COLUMNS 2ND FLOOR ADD MID SPAN BLKS VERT, COL. STUDS ARE FLAT
11) TIE SHEARWALLS TO TRUSS BOTTOM CHORD, AT FRONT SHEARWALLS (A3.5 16" ON CENTER)
04/17/2007 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
03/21/2007 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*