Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/29/2008 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 04/22/2008 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* | |
| 04/21/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. ONLY ONE CONDUCTOR PER TERMINAL LUG 2. BONDING JUMPER TO BE AS PER 250.102 & 250.66 3. USE APPROVED SIZED WIRE NUTS FOR CONDUCTORS 4. INSTALL MAIN BUILDING JUMPER AT DISCONNECT 5. LABEL PANEL COVER AS PER 200.5 6. WHERE IS NEW GROUNDING ELECTRODE SYSTEM FOR SEPARATELY DERIVED SYSTEM? |
|
| 04/11/2008 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* UNNECESSARY INSPECTIONS MAY RESULT IN A REFEE |
|
| 04/10/2008 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* |