Permit: T07CM01001

Parcel: 11016223A


Addresses:

5981 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T07CM01001

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
04/29/2008 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
04/22/2008 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
04/21/2008 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. ONLY ONE CONDUCTOR PER TERMINAL LUG
2. BONDING JUMPER TO BE AS PER 250.102 & 250.66
3. USE APPROVED SIZED WIRE NUTS FOR CONDUCTORS
4. INSTALL MAIN BUILDING JUMPER AT DISCONNECT
5. LABEL PANEL COVER AS PER 200.5
6. WHERE IS NEW GROUNDING ELECTRODE SYSTEM FOR SEPARATELY DERIVED SYSTEM?
04/11/2008 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
UNNECESSARY INSPECTIONS MAY RESULT IN A REFEE
04/10/2008 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*