Permit: T07CM01001

Parcel: 11016223A


Addresses:

5981 E GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
04/29/2008 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
04/10/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
02/26/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK AT DRIVE FOR CANOPIES

1. 300.5
02/11/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK DATA & FEEDER PVC CONDUITS
TEP TO PREVIOUS INSPECTION
11/14/2007 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
1. PLEASE VERIFY GRADE FOR REQUIREMENTS OF 300.5 - 2' UNDER DRIVE & PARKING
2. STRAIGHTEN CONDUCTOR 3RD POLE IN AND CUT 1ST & 2ND CONDUCTORS LOOSE
09/05/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 2 - 3", 1 - 4", 1 - 2" PVC UNDER SLAB