Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00998
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/23/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/20/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 11/12/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 11/10/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. BOND JUMPERS TO BE AS PER 250.102 & 250.66 2. SEPARATELY DERIVED GROUNDING ELECTRODE CONDUCTOR TO BE CONTINUOUS TO GROUND 3. 9 KVA TRANSFORMER NEED 6" PER LABEL AND 450.9 |