Permit: T07CM00998

Parcel: 11016223A


Addresses:

5977 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00998

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/23/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/20/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
11/12/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
11/10/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. BOND JUMPERS TO BE AS PER 250.102 & 250.66
2. SEPARATELY DERIVED GROUNDING ELECTRODE CONDUCTOR TO BE CONTINUOUS TO GROUND
3. 9 KVA TRANSFORMER NEED 6" PER LABEL AND 450.9