Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T07CM00987
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/14/2007 | PLUMBING - FINAL | Approved | ||
06/08/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CRITICAL LEVEL OF FLUSH-O-METER SHALL BE 6" ABOVE THE HIGHEST PART OF URINAL. (603.4.1) |
|
06/06/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. FINISH URINAL 2. OK TO RESET OFFSET WATER CLOSET |
|
05/31/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. MENS HC WATER CLOSET DOES NOT HAVE CLEARANCES 2. HAMMER ARRESTORS, TRAP PRIMER, AIR ADMITTANCE VALVE TO BE ACCESSIBLE. DID NOT GO ONTO ROOF |
|
05/24/2007 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1. FIXTURES INSTALLED IN ALL AREAS EXCEPT IN MENS ONLY AREA. PLUMBERS STILL WORKING. 2. NO SERIOUS SAFETY HAZARDS EXIST IN PLUMBING. I HAVE NO PROBLEM WITH TCO 3. FIXTURES NOT INSTALLED SHALL HAVE PIPING CAPPED OR PLUGGED. 4. URINALS REQUIRE 3/4" WATER SUPPLY 5. EXISTING HB ON ROOF REQUIRES VAC BREAKER VENT THROUGH ROOF REQUIRE PAINT. 6. ROOF DRAINS REQUIRE STRAINERS. |
|
05/23/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* |