Permit: T07CM00987

Parcel: 10409002D


Addresses:

475 W WETMORE RD


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T07CM00987

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/16/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
OK TO COVER ALL AREAS
05/15/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
SUPPORT PIPE AS REQUIRED
05/14/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) NO TEST ON ABS
2) SUPPORT ALL PIPE TO TABLE 3-2 2003 UPC
3) SECURE CLOSET FLANGES TO FLOOR
4) INSPECTION STOPPED
05/11/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) AFTER HRS INSPECTION PAID WITH CHECK #24681
2) POST YOUR ADDRESS
3) PROVIDE WATER TEST ON DWV
4) INSTALL WATER PIPING PER PLAN
5) SUPPORTS ON ABS NOT TO EXCEED 4'
6) 120 PSI TEST ON WATER
7) YOU MAY COVER 1" DROPS TO WCS THAT DO NOT HAVE 3/4" HOSE BIBS CONNECTED TO AS THIS MAY OVER TAX SUPPLY TO FLUSH? METERS
8) ROOF DRAINS UNDER TEST. YOU MAY COVER VERTICAL DROPS. RED LINE CHANGES
9) YOU MAY COVER AREAS WITHOUT PLUMBING