Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2007 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* VERTICAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP SEE 706.4 2003 UPC WHERE A VENT CONNECTS TO A HORIZONTAL DRAIN, IT SHALL HAVE ITS INVERT TAKEN OFF ABOVE THE DRAINAGE CENTER LINE DOWNSTREAM OF THE TRAP BEING SERVED 905.2 UPC REINSPECTED 2:00 PM 1. CORRECTIONS MADE OK 2. OK TO COVER 3. OK FOR CONCRETE |
|
| 04/18/2007 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1. NOT INSTALLED PER PLAN NO REDLINES ON SITE INSTALLATION DOES NOT MEET CODE 2. WHERE A VENT CONNECTS TO A HORIZONTAL DRAIN IT SHALL HAVE ITS INVERT TAKEN OFF ABOVE THE DRAINAGE CENTER LINE DOWNSTREAM OF THE TRAP BEING SERVED. 3. MAY NOT INTERMINGLE MATERIAL TYPES 4. MAY NOT CONNECT CONDENSATE WASTE TO SANITARY SEWER. 5. PIPE NOT COMPLETELY WRAPPED IN FOOTING 6. NO SOFT SOLDER BELOW THE FLOOR 7. ALL FIXTURES TO BE VENTED HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP VERTICAL X HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP |