Permit: T07CM00987

Parcel: 10409002D


Addresses:

475 W WETMORE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00987

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/24/2007 ELECTRIC - FINAL Approved FINAL OK AS PER C.CLEMENS LAST INSPECTION
05/23/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED PROTECTIVE BUSHING #4 & LARGER CONDUCTORS
NEC 300.4F
2. IDENTIFY PANEL AT ITS FEEDER DISCONNECT - NEC 110.22
3. PROVIDE GFI PROTECTION FOR BATHROOM RECEPTACLES
NEC 210.8 B
4. IDENTIFY ROOFTOP UNIT DATA PLATE & DISCONNECT
5. IDENTIFY EX. FAN DISCONNECT
6. EXTERIOR LIGHTING TO MEET CITY LIGHTING CODE, PROPERLY MOUNT EXTERIOR EMERGENCY LIGHT. ALL EMERGENCY LIGHTING TO BE FED BY THE NORMAL LIGHTING CKT FOR THAT AREA -- SEE NEC 700.12
7. REVISE PLANS TO SHOW ACTUAL SCOPE OF WORK.
05/22/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. WORK IN PROGRESS - DO NOT CALL BEFORE READY
2. WORK TO BE PER PLAN OR PLANS REVISED TO SHOW ACTUAL SCOPE OF WORK.