Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00987
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/24/2007 | ELECTRIC - FINAL | Approved | FINAL OK AS PER C.CLEMENS LAST INSPECTION | |
05/23/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED PROTECTIVE BUSHING #4 & LARGER CONDUCTORS NEC 300.4F 2. IDENTIFY PANEL AT ITS FEEDER DISCONNECT - NEC 110.22 3. PROVIDE GFI PROTECTION FOR BATHROOM RECEPTACLES NEC 210.8 B 4. IDENTIFY ROOFTOP UNIT DATA PLATE & DISCONNECT 5. IDENTIFY EX. FAN DISCONNECT 6. EXTERIOR LIGHTING TO MEET CITY LIGHTING CODE, PROPERLY MOUNT EXTERIOR EMERGENCY LIGHT. ALL EMERGENCY LIGHTING TO BE FED BY THE NORMAL LIGHTING CKT FOR THAT AREA -- SEE NEC 700.12 7. REVISE PLANS TO SHOW ACTUAL SCOPE OF WORK. |
|
05/22/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. WORK IN PROGRESS - DO NOT CALL BEFORE READY 2. WORK TO BE PER PLAN OR PLANS REVISED TO SHOW ACTUAL SCOPE OF WORK. |