Permit: T07CM00980

Parcel: 12218234A

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
12/19/2007 FIRE - FINAL Approved
11/07/2007 FIRE - FINAL Denied 1. Need up to date sprinkler inspection and 5 year check valve inspection.
2. Need as-bults showing proper sprinkler coverage in lobby area.
10/24/2007 FIRE - FINAL Denied 1. Lower sprinkler heads below drop ceiling, in storage area 2nd floor.
2. Need up to date sprinkler inspection and 5 year check valve inspection.
3. Need as-bults showing proper sprinkler coverage in lobby area. Plans show 4 heads when actually 2 heads on site.