Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/19/2007 | FIRE SPKLR - FINAL | Approved | ||
| 10/24/2007 | FIRE SPKLR - FINAL | Denied | 1. Lower sprinkler heads below drop ceiling, in storage area 2nd floor. 2. Need up to date sprinkler inspection and 5 year check valve inspection. 3. Need as-bults showing proper sprinkler coverage in lobby area. Plans show 4 heads when actually 2 heads on site. |