Permit: T07CM00972

Parcel: 140325230


Addresses:

3927 E ISAIAH DR


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T07CM00972

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
08/09/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
08/02/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/01/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REAR MIDDLE #6 SHEARWALL NOT INSTALLED
2) REAR MIDDLE #6 HOLDOWNS WRONG LOCATIONS
3) PROVIDE APPROVED GABLE END TRUSS REPAIRS FOR NOTCHES
4) NO CITY APPROVED TRUSS DRAWINGS ON SITE
5) NO LADDER ACCESS TO ROOF
6) STOPPED INSPECTION TO MANY ITEMS
07/26/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEMS 3 & 4 OF 7/20/07 INSPECTION NOT DONE
2) TRUSSES ARE NOT PER TRUSS PLAN
3) GABLE END TRUSSES 2 X 4 TOP PLATES NOTCHED FOR LOOK OUTS. PROVIDE APPROVED REPAIR DOCUMENTS
4) NO LADDER ACCESS TO ROOF
07/20/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GARAGE 4 X 12 HEADER CUT MORE THAN 25 ?
2) 2-16D NAILS REQUIRED ON ENDS OF DIAGONAL BRACES
3) STRAP NON OVER LAPPING DBL TOP PLATES AT CORNERS
4) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF PLATE SURFACES
5) NO TRUSS DRAWINGS ON SITE
6) NO LADDER ACCESS TO ROOF
7) STOPPED INSPECTION