Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T07CM00966

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/17/2007 BUILDING - FINAL Approved IVRS - Inspection :*
08/16/2007 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
08/14/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REPAIR STUCCO BACK PORCH
2) NO DEAD FRONT COVER EAST A/C DISCONNECT
3) TERMINATE WIRE SECURITY PANEL
4) NEED VACUUM BREAKER HOSE BIB AT ENTRANCE PIPE
5) TRACER WIRE FOR SEWER MUST BE ACCESSIBLE
6) SECURE A/C WHIPS WITHIN 12" OF DISCONNECT
7) NEED SECONDARY CONDENSATE DRAINS OR CUT OFF SWITCHES ON BOTH FURNACES
8) SECURE DISHWASHER DRAIN HOSE TO HIGH POINT UNDER COUNTER
9) NEED GAS SHUT OFF FOR FIREPLACE THAT IS READILY ACCESSIBLE AND SERVES NO OTHER APPLIANCE