Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
07/31/2008 MECHANICAL - HOODS Approved IVRS - Inspection :*
MET WITH MECHANICAL CONTRACTOR ON SITE, WE BOTH INSPECTED THE DUCT ANGLE AND AGREED THAT ALTHOUGH MARGINAL, THIS SYSTEM DOES FALL WITHIN THE PARAMETERS OF THE I.M.C GREASE DUCT ACCESS DOORS NOT REQUIRED.
05/01/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1ST LAYER OF GREASE DUCT WRAP OK
CALL SECOND LAYER INSPECTION WITH ABOVE CEILING
04/23/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
MECH. HOODS LEAK TEST OK, INSTALL 1ST LAYER OF GREASE DUCT WRAP
04/15/2008 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*