Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/24/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* PROVIDE ACCESS DOORS ON GREASE DUCT OK FOR TILES ALL AREAS MECHANICAL ONLY |
|
| 04/23/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* ABOVE CEILING OK TO INSTALL GRID |
|
| 04/15/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. NO SINGLE WALL PIPE THROUGH CEILING AT W/H 2. PROVIDE PROPER CLEARANCE TO TRUSS FOR DUCT WRAP 3. PROVIDE PROPER SPACING GREASE DUCT TO FAN 4. NO SCREWS IN GREASE DUCT 5. PROVIDE METAL ON WALL 18" UP FROM HOOD |