Permit: T07CM00962

Parcel: 117120210


Addresses:

63 E CONGRESS ST

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
07/31/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
2ND FLOOR OK TO COVER
2ND FLOOR CLOSET FLANGE OK
OK TO COVER ALL AREAS
07/30/2008 PLUMBING - INTERMEDIATE Partial Approval 1. WHO INSPECTED UPSTAIRS? CONTRACTOR HAS NOT ASKED ME TO INSPECT ANYTHING UPSTAIRS EXCEPT FOR THE CLOSET FLANGES. I NOTICED OVERHEAD ABS IS NOT SUPPORTED PROPERLY
I DON'T KNOW WHAT IS IN THE WALLS
CLOSET FLANGES FIRST FLOOR OK
06/04/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
HYDROMECHANICAL GREASE INTERCEPTOR INSTALLED OK
05/07/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
SEE NOTE #7 FROM 3/25/08
ABS WATER TEST OK
COPPER OK
NEED TO SEE CLOSET FLANGES
OK TO COVER WALLS WITH EXCEPTION
03/25/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES, THEN NO MORE THAN 4' BETWEEN HANGERS
2. VERTICAL PIPING TO BE SUPPORTED WITH APPROVED STRAPS
3. PIPING TO BE PROTECTED FROM METAL STUDS
4. ALL FIXTURE TRAPS TO BE VENTED
5. GREASE TRAP NOT APPROVED
6. WILL REQUIRE PLUMBING SPEC'S
7. EACH FIXTURE TIED INTO GREASE TRAP WILL REQUIRE A FLOW CONTROL IN A READILY ACCESSIBLE AND VISIBLE LOCATION
8. NO SYSTEM VENT BETWEEN FLOW CONTROL AND G.T
9. THIS IS NOT A COMPLETE LIST
10. HAVE PLUMBER ON SITE AT TIME OF NEXT INSPECTION