Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 2ND FLOOR OK TO COVER 2ND FLOOR CLOSET FLANGE OK OK TO COVER ALL AREAS |
|
| 07/30/2008 | PLUMBING - INTERMEDIATE | Partial Approval | 1. WHO INSPECTED UPSTAIRS? CONTRACTOR HAS NOT ASKED ME TO INSPECT ANYTHING UPSTAIRS EXCEPT FOR THE CLOSET FLANGES. I NOTICED OVERHEAD ABS IS NOT SUPPORTED PROPERLY I DON'T KNOW WHAT IS IN THE WALLS CLOSET FLANGES FIRST FLOOR OK |
|
| 06/04/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* HYDROMECHANICAL GREASE INTERCEPTOR INSTALLED OK |
|
| 05/07/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SEE NOTE #7 FROM 3/25/08 ABS WATER TEST OK COPPER OK NEED TO SEE CLOSET FLANGES OK TO COVER WALLS WITH EXCEPTION |
|
| 03/25/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES, THEN NO MORE THAN 4' BETWEEN HANGERS 2. VERTICAL PIPING TO BE SUPPORTED WITH APPROVED STRAPS 3. PIPING TO BE PROTECTED FROM METAL STUDS 4. ALL FIXTURE TRAPS TO BE VENTED 5. GREASE TRAP NOT APPROVED 6. WILL REQUIRE PLUMBING SPEC'S 7. EACH FIXTURE TIED INTO GREASE TRAP WILL REQUIRE A FLOW CONTROL IN A READILY ACCESSIBLE AND VISIBLE LOCATION 8. NO SYSTEM VENT BETWEEN FLOW CONTROL AND G.T 9. THIS IS NOT A COMPLETE LIST 10. HAVE PLUMBER ON SITE AT TIME OF NEXT INSPECTION |