Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2008 | ELECTRIC - FINAL | Approved | PER ON-SITE INSPECTION WITH DAN SANTACRUZ AND SUBSEQUENT INFORMATION PROVIDED TO SHOW RELAYS AND PENDANDT LIGHTS AS MEETING LISTING REQUIREMENTS OF NEC. | |
| 09/03/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PANEL DIRECTORIES TO BE AS PER 408.4 - NO ABBREVIATIONS 2. WALK-IN BOX AIR HANDLER NEEDS SWITCH & ROOF UNIT NEEDS DISCONNECT 3. DISHWASHER RECEPTACLE IS WET LOCATION 4. CONTACTORS TO BE LISTED 5. KITCHEN RECEPTACLES TO BE GFCI 210.8 (B) 6. NEED ANSUL INSTRUCTIONS FOR MAKE UP WE HAVE EXPOSED CONDUCTORS 7. BOXES IN NON-COMBUSTIBLE TO BE NO MORE THAN 1/4" -- 314.20 8. LIGHT FIXTURES TO BE LISTED |