Permit: T07CM00962

Parcel: 117120210


Addresses:

63 E CONGRESS ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/10/2008 ELECTRIC - FINAL Approved PER ON-SITE INSPECTION WITH DAN SANTACRUZ AND SUBSEQUENT INFORMATION PROVIDED TO SHOW RELAYS AND PENDANDT LIGHTS AS MEETING LISTING REQUIREMENTS OF NEC.
09/03/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PANEL DIRECTORIES TO BE AS PER 408.4 -
NO ABBREVIATIONS
2. WALK-IN BOX AIR HANDLER NEEDS SWITCH & ROOF UNIT NEEDS DISCONNECT
3. DISHWASHER RECEPTACLE IS WET LOCATION
4. CONTACTORS TO BE LISTED
5. KITCHEN RECEPTACLES TO BE GFCI 210.8 (B)
6. NEED ANSUL INSTRUCTIONS FOR MAKE UP
WE HAVE EXPOSED CONDUCTORS
7. BOXES IN NON-COMBUSTIBLE TO BE NO
MORE THAN 1/4" -- 314.20
8. LIGHT FIXTURES TO BE LISTED