Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2008 | ELECTRIC - CABLE DROP | Approved | ||
| 08/11/2008 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* | |
| 08/05/2008 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* | |
| 07/30/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 06/23/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION - CONTRACTOR NOT ON SITE 1. PLANS CALL FOR LESS THAN 10' OF SERVICE CONDUCTORS 2. GROUNDING ELECTRODE & PIPE BONDING CONDUCTORS TO TERMINATE IN SERVICE DISCONNECT ENCLOSURE 3. HAVE INCORRECT GROUND ROD CLAMPS - RODS TO BE MIN. 6' APART 4. BOND METAL PIPING 5. NEED BUSHING #4 & LARGER CONDUCTOR 6. TIGHTEN FITTINGS & CONNECTIONS 7. GROUNDS #6 & SMALLER TO BE GREEN ENTIRE LENGTH |
|