Permit: T07CM00962

Parcel: 117120210


Addresses:

63 E CONGRESS ST

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
09/10/2008 ELECTRIC - CABLE DROP Approved
08/11/2008 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
08/05/2008 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
07/30/2008 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
06/23/2008 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION - CONTRACTOR NOT ON SITE

1. PLANS CALL FOR LESS THAN 10' OF SERVICE CONDUCTORS
2. GROUNDING ELECTRODE & PIPE BONDING CONDUCTORS TO TERMINATE IN SERVICE DISCONNECT ENCLOSURE
3. HAVE INCORRECT GROUND ROD CLAMPS -
RODS TO BE MIN. 6' APART
4. BOND METAL PIPING
5. NEED BUSHING #4 & LARGER CONDUCTOR
6. TIGHTEN FITTINGS & CONNECTIONS
7. GROUNDS #6 & SMALLER TO BE GREEN ENTIRE LENGTH
04/15/2008 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*