Permit: T07CM00962

Parcel: 117120210


Addresses:

63 E CONGRESS ST

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
09/10/2008 ELECTRIC - ABOVE CEILING Approved
08/05/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO TILE
OK TEMP POWER FOR TEST
SUBJECT TO POSTING OF BOND
07/30/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SEAL RACEWAY TO WALK-IN BOX PER 300.7
2. M/C TO BE AS PER 334.20 - 12" & 6" - 300.11
3. FINISH MEZZANINE LIGHTS
4. FILL UNUSED OPENING IN BOX COVER - NOT FITTING
5. GROUNDING ELECTRODE CONDUCTOR TO BE SIZED
PER 250.66
6. PLEASE REVISE SERVICE DRAWING - NOT REFLECTIVE OF WORK INSTALLED
7. A BOND WILL NEED TO BE POSTED FOR POWER
07/24/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FIXTURES TO BE ATTACHED TO CEILING GRID
2. NEED TIE WIRE FROM FIXTURE TO BUILDING STRUCTURE
3. CLOSE OPEN JUNCTION BOXES
4. STRAP MC CABLE WITHIN 12" OF JUNCTION BOX
5. IS WALK IN COOLER WIRED?
6. WHERE ARE "F" FIXTURES?
03/25/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*