Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2008 | ELECTRIC - ABOVE CEILING | Approved | ||
| 08/05/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO TILE OK TEMP POWER FOR TEST SUBJECT TO POSTING OF BOND |
|
| 07/30/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SEAL RACEWAY TO WALK-IN BOX PER 300.7 2. M/C TO BE AS PER 334.20 - 12" & 6" - 300.11 3. FINISH MEZZANINE LIGHTS 4. FILL UNUSED OPENING IN BOX COVER - NOT FITTING 5. GROUNDING ELECTRODE CONDUCTOR TO BE SIZED PER 250.66 6. PLEASE REVISE SERVICE DRAWING - NOT REFLECTIVE OF WORK INSTALLED 7. A BOND WILL NEED TO BE POSTED FOR POWER |
|
| 07/24/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FIXTURES TO BE ATTACHED TO CEILING GRID 2. NEED TIE WIRE FROM FIXTURE TO BUILDING STRUCTURE 3. CLOSE OPEN JUNCTION BOXES 4. STRAP MC CABLE WITHIN 12" OF JUNCTION BOX 5. IS WALK IN COOLER WIRED? 6. WHERE ARE "F" FIXTURES? |
|
| 03/25/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |