Permit: T07CM00962

Parcel: 117120210


Addresses:

63 E CONGRESS ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/10/2008 ELECTRIC - INTERMEDIATE Approved
04/15/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL & HARD LID COVER
SINGLE LINE DIAGRAM TO BE REVISED TO SHOW ACTUAL INSTALLATION. VERIFY ACCEPTABLE GROUNDING ELECTRODE SYSTEM FOR SERVICE
03/25/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NAIL PLATES NEEDED FOR MC & LV WIRING WHERE
HOLE IS 1/4" OR LESS FROM STUD FACE
2. MC TO BE SECURED WITHIN 12" OF TERMINATIONS
AND SUPPORT AND MAX 6' INTERVAL

TOM (SUPER) 907-7139