Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T07CM00961

Parcel: 133152900

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
06/18/2007 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
05/08/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. HW KINK CORRECTION OK
2. FS ROUGH AND INTERMEDIATE FOR RM 108 W/TEST TO REVENT IS OK TO COVER.
3. INSTALL HANGER AT REVENT CONNECTION ABV CEILING.
4. PLUG FLOOR DRAINS DURING CONSTRUCTION.
05/07/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
PIPING AT 3-COMP SINK & HB OK TO COVER
CORRECT CRUSHED 3/4" HW BELOW SLAB
05/04/2007 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 90 DEG. MAX CHANGE OF DIRECTION ON TRAP ARM. SWEEP REQUIRED.
2. PIPE HS DRAIN BELOW CONCRETE, PROVIDE TEST WYE AND HAVE ALL CONNECTIONS MADE FOR INSP.
3. BRAZE WATER PIPING AND TURN UP IN WALL.
05/02/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
TEST ON KIT WASTE OK
CONNECT PIPING TO EXISTING AND RECALL FOR INSP.
04/02/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
BAR SINK AREA APPROVED PER APPROVED PLAN
PIPE WRAPS THIS AREA OK
03/30/2007 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE MINIMUM REQUIRED SLOPE PER SEC 708

PLAN HAS DISCREPANCY BETWEEN P-1 AND P-2
HAND SINK REQUIRES A DIRECT CONNECTION
SUPPORT FS TRAP ARM
INSTALL FS AT CORRECT HEIGHT