| 06/25/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/19/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SATELLITE TV TO BE GROUNDED PER 820.40 2. WAITING ON PLAN REVISIONS OK TCO SUBJECT TO DETERMINATION OF S.LONG |
|
| 06/18/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. EXISTING BREAKERS SHOULD BE AS PER MANUFACTURES LISTING. 2. LIGHTING PLAN NOT REFLECTIVE OF WORK INSTALLED PLEASE REVISE 3. EM LIGHTING TO BE AS PER 700.12 4. REMOVE UNSAFE CORDS FROM EXTERIOR EQUIPMENT TO BE LISTED CORD & PLUG CONNECTED |