Permit: T07CM00940

Parcel: 134242460


Addresses:

6655 E 22ND ST

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
10/22/2007 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
ON FINAL PROVIDE MIN. 2" R8 DUCT LINER IN EXPOSED DUCT ON ROOF. SEAL ALL LEADING EDGES OF DUCT LINER.
OK FOR SHEETROCK.
09/21/2007 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
WATER HEATER VENT DOES NOT HAVE MIN. CLEARANCE TO COMBUSTIBLES. COMBUSTION AIR NOT IN W/H ROOM
09/13/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
PROVIDE COMBUSTION AIR TO WATER HEATER ROOM
WATER HEATER VENT DOES NOT HAVE ADEQUATE CLEARANCE
COMBUSTIBLES NOT ALLOWED IN A RETURN PLENUM
OK FOR PARTIAL SHEETROCK