Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/07/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/07/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SERVICE INSPECTION |
|
| 11/05/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE PAINT AT GROUND CLAMP CONNECTION AT WATER PIPE - NEC 250.12 2. CONNECT GROUNDING ELECTRODE TAP TO COMMON GROUNDING ELECTRODE CONDUCTOR - NEC 250.64(D) 3. BOND GAS PIPING TO SERVICE -- NEC 250.104 4. PROPERLY INSTALL DOUBLE LUG IN 200 AMP DISCONNECT 5. MARK "SERVICE DISCONNECTS" NEC 230.70 6. 4/0 ALUMINUM CONDUCTORS NOT RATED FOR 200 AMP COMMERCIAL SERVICE, NEC 310.16 7. VERIFY EXISTING CONDUCTORS ARE SUNLIGHT RESISTANT NEC 310.8 |
|
| 09/13/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK WALLS 2. OK CEILINGS |
|
| 08/30/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BRANCH CIRCUITS SERVING PATIENT CARE AREAS (EXAM ROOMS) NEED TO BE WIRED PER NEC 517.13 2. INSTALL NAIL PLATES ON BURIED HOLES LESS THAN 1 1/4" TO FACE OF STUD - NEC 300.4(A)(1) 3. PROTECT CABLES WHERE RUN PARALLEL WITH FRAMING MEMBERS & LESS THAN 1 1/4" FROM FACE OF STUD OR FURRING STRAP - NEC 300.4(D) |