Permit: T07CM00940

Parcel: 134242460


Addresses:

6655 E 22ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
12/07/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/07/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
SERVICE INSPECTION
11/05/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE PAINT AT GROUND CLAMP CONNECTION AT WATER PIPE - NEC 250.12
2. CONNECT GROUNDING ELECTRODE TAP TO COMMON GROUNDING ELECTRODE CONDUCTOR - NEC 250.64(D)
3. BOND GAS PIPING TO SERVICE -- NEC 250.104
4. PROPERLY INSTALL DOUBLE LUG IN 200 AMP DISCONNECT
5. MARK "SERVICE DISCONNECTS" NEC 230.70
6. 4/0 ALUMINUM CONDUCTORS NOT RATED FOR 200 AMP COMMERCIAL SERVICE, NEC 310.16
7. VERIFY EXISTING CONDUCTORS ARE SUNLIGHT RESISTANT
NEC 310.8
09/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK WALLS
2. OK CEILINGS
08/30/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BRANCH CIRCUITS SERVING PATIENT CARE AREAS (EXAM ROOMS) NEED TO BE WIRED PER NEC 517.13
2. INSTALL NAIL PLATES ON BURIED HOLES LESS THAN 1 1/4" TO FACE OF STUD - NEC 300.4(A)(1)
3. PROTECT CABLES WHERE RUN PARALLEL WITH FRAMING MEMBERS & LESS THAN 1 1/4" FROM FACE OF STUD OR FURRING STRAP - NEC 300.4(D)