Permit: T07CM00907

Parcel: 12315107A


Addresses:

700 E ADAMS ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07CM00907

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/24/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
04/02/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE A 1/2" GAS LINE TO FURNACE
2. ELEC. DISCONNECT IS OVERFUSED
3. PROVIDE A ROOF JACK WHERE ELEC. CONDUIT PENETRATES THE ROOF.
4. PROVIDE A PRESSURE TEST ON GAS PIPING.
5. GAS FLEX ON WATER HEATER DOES NOT EXCEED 3' IN LENGTH.
6. PROVIDE MIN. 1" CLEARANCE FROM COMBUSTIBLES AROUND WATER HEATER VENT.
7. ID CIRCUIT BREAKER