Permit: T07CM00906

Parcel: 12315107B


Addresses:

694 E ADAMS ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00906

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/25/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/18/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEAL OPENING IN TOP OF WATER HEATER ENCLOSURE
2. CANNOT USE #14 FOR GROUNDING CONDUCTOR ON 30 AMP. CIRCUIT MUST USE #10 -- NEC 250.122
3. CANNOT USE WHITE WIRE AS PHASE CONDUCTOR
NEC 200.6, 200.7, 310.12
4. CLEARLY IDENTIFY WATER HEATER CIRCUIT. DO NOT USE ABBREVIATIONS NEC 408.4