Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/18/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEAL OPENING IN TOP OF WATER HEATER ENCLOSURE 2. CANNOT USE #14 FOR GROUNDING CONDUCTOR ON 30 AMP. CIRCUIT MUST USE #10 -- NEC 250.122 3. CANNOT USE WHITE WIRE AS PHASE CONDUCTOR NEC 200.6, 200.7, 310.12 4. CLEARLY IDENTIFY WATER HEATER CIRCUIT. DO NOT USE ABBREVIATIONS NEC 408.4 |