Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00906
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/25/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/18/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEAL OPENING IN TOP OF WATER HEATER ENCLOSURE 2. CANNOT USE #14 FOR GROUNDING CONDUCTOR ON 30 AMP. CIRCUIT MUST USE #10 -- NEC 250.122 3. CANNOT USE WHITE WIRE AS PHASE CONDUCTOR NEC 200.6, 200.7, 310.12 4. CLEARLY IDENTIFY WATER HEATER CIRCUIT. DO NOT USE ABBREVIATIONS NEC 408.4 |