Permit: T07CM00904

Parcel: 133243720

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
11/01/2007 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
OK FOR CEILING TILES
WILL CHECK CONDENSATE FROM FRONT UNIT ON FINAL
FIRE WRAP IS OK
10/18/2007 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
- FLEX DUCTING NOT INSTALLED PER DETAILS ON PLANS.
- USE ONLY UL 181 LISTED TAPE
- PROVIDE A 100 WATT LIGHT TEST OR A SMOKE TEST ON GREASE DUCT.