Permit: T07CM00904

Parcel: 133243720

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T07CM00904

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
12/19/2007 PLUMBING - GAS PRESSURE TEST Approved
12/12/2007 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
TEST FROM METER TO ALL APPLIANCES PER REVISED PLAN DATED 11/30/07 FROM SMU ENGINEERING WHICH SHALL BE CITY APPROVED PLAN CHECK STAMPED.

1. SHALL PROVIDE COMBUSTION AIR FOR WATER HEATER PER PLAN TO OBTAIN GAS CARD.
11/23/2007 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
- PIPING IS NOT INSTALLED PER PLAN
- 2" AT 400' IS UNDERSIZED
- PROVIDE AN ACCURATE PLAN; IE DISTANCE, SIZE AND FURNACE
- COMPLETE WH VENT AND INSTALL CABLE RESTRAINTS
- COMPLETE WH T&P DRAIN
10/25/2007 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
CANCELLED
10/24/2007 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
PROVIDE APPROVAL FROM CITY OF TUCSON FOR NEW GAS PIPING
08/14/2007 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
GAS PIPING INSIDE BUILDING OK