Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T07CM00904
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/19/2007 | PLUMBING - GAS PRESSURE TEST | Approved | ||
12/12/2007 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* TEST FROM METER TO ALL APPLIANCES PER REVISED PLAN DATED 11/30/07 FROM SMU ENGINEERING WHICH SHALL BE CITY APPROVED PLAN CHECK STAMPED. 1. SHALL PROVIDE COMBUSTION AIR FOR WATER HEATER PER PLAN TO OBTAIN GAS CARD. |
|
11/23/2007 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* - PIPING IS NOT INSTALLED PER PLAN - 2" AT 400' IS UNDERSIZED - PROVIDE AN ACCURATE PLAN; IE DISTANCE, SIZE AND FURNACE - COMPLETE WH VENT AND INSTALL CABLE RESTRAINTS - COMPLETE WH T&P DRAIN |
|
10/25/2007 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
10/24/2007 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* PROVIDE APPROVAL FROM CITY OF TUCSON FOR NEW GAS PIPING |
|
08/14/2007 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* GAS PIPING INSIDE BUILDING OK |