Permit: T07CM00904

Parcel: 133243720

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T07CM00904

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/14/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
08/10/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) AT K-4 LIMIT CHANGES OF DIRECTION OF TRAP ARMS TO 90 DEGREE
2) TRAP AND TA SHALL BE THE SAME SIZE
3) INSTALL SAFETY PLATES IF PIPING IS WITHIN 1" OF STUD WALL
4) CORRECT BURNED PVC AT OTHER HS
5) INSTALL INSULATION PER MANUFACTURES INSTRUCTIONS. SEAL WITH ADHESSIVE AT ALL JOINTS
6) LETTER RECEIVED FOR SPEC CHANGES
08/08/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PIPE INSULATION NOT PER SPEC.
- NEED PLAN REVISION OR LETTER FROM ENGINEER PRIOR TO COVERING.
- SECURE TUBING W/APPROVED CLAMPS. CU CLAMPS ARE NOT ALLOWED ON PLASTIC
- SECURE ISOLATORS AND PROTECT TUBING FROM METAL
- ADHESIVE TAPE NOT ALLOWED ON PEX
- HAMMER ARRESTORS NOT INSTALLED
- DOUBLE FIXTURE FITTINGS REQUIRED AT LAVS
- FIPS CANNOT BE CONCEALED USE MIP OR SOLVENT WELD URINAL FLANGE.
- SUPPORT HORIZONTAL VENTS
- PROTECT PVC FROM SHARP EDGES
- LIMIT 1 1/2" TRAP ARM TO 90 DEG. CHANGE OF DIRECTION
- GT CONNECTIONS OK USE FRANK PATTERN CO COVERS
- GAS INSIDE OK
- CLOSET FLANGES ARE REQUIRED TO SET ON FF
- RECALL FOR CLOSET FLANGE INSP. AFTER TILE
- LAV CARRIERS NOT YET INSTALLED
- NEED BACKING AT MS