Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00904
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/07/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/02/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH ITEMS 5, 6, 7, 8, 9 & 12 |
|
12/28/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE - 314.20 2. ALL KITCHEN RECEPTACLES TO BE AS PER 210.8 3. REMOVE 110V POWER FROM ANSUL BOX INSTALL IN JUNCTION BOX 4. RECEPTACLES UNDER HOOD TO DISCONNECT UPON ACTIVATION OF ANSUL 5. SEAL CONDUITS TO WALK IN AS PER 300.7 6. WHERE ARE DISCONNECTING MEANS FOR WALK-IN LOWER UNITS 7. LABEL TIME CLOCKS 8. NEED PERMANENT CIRCUIT DIRECTORIES AS PER 408.4 9. WHERE IS DISCONNECTING MEANS FOR ICE MACHINE 10. VERIFY LISTING LABEL FOR ICE MACHINE 11. EM & EXIT LIGHTS TO BE AS PER 700.12 12. NEED MAKE UP AIR CONTROL DIAGRAM ROOF: 1. TIGHTEN LOOSE FITTINGS 2. USE APPROVED FITTINGS 3. MAINTAIN WORKING CLEARANCES 4. LABEL DISCONNECTS 5. CANNOT USE CORDS IN RACEWAYS FOR PERMANENT WIRING 6. BOND ENCLOSURE |