Permit: T07CM00904

Parcel: 133243720

Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T07CM00904

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Approved

Date Description Inspector Results Comments
01/07/2008 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection :*
01/02/2008 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
12/28/2007 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
09/20/2007 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
1) SERVICE CLEARANCE BASED ON PENDING REVISION FOR CHANG IN CONDUCTOR SIZES
2) CONRACTOR HAD RECEIPT FOR POSTING OF BOND
09/19/2007 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*
1) NEED TO POST BOND FOR TEMP POWER
2) FINISH WORK AT SERVICE
3) PLAN CALLS FOR 4/0 TO FFED 200 AMP PANEL
4) PLAN CALLS FOR 350 MCM TO FEET CT CAN.
5) INSTALL PER PLAN OR REVISE DRAWINGS
6) BRACE CONDUCTORS PER INSTRUCTION O DOOR OF CT CAN.
7) RECALL WHEN READY
08/22/2007 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*
1. SHEETMETAL SCREWS NOT ALLOWED FOR BONDING 250.8
2. TEMP POWER FOR TEST IS TO TEST EQUIPMENT RIGHT BEFORE FINAL

OK CANS IN SOFFIT -- RECEPTIONIST