Inspection History: ELECTRIC - TEMP POWER FOR TEST
Permit Number - T07CM00904
Inspection Description - ELECTRIC - TEMP POWER FOR TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/07/2008 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* | |
01/02/2008 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* | |
12/28/2007 | ELECTRIC - TEMP POWER FOR TEST | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
09/20/2007 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* 1) SERVICE CLEARANCE BASED ON PENDING REVISION FOR CHANG IN CONDUCTOR SIZES 2) CONRACTOR HAD RECEIPT FOR POSTING OF BOND |
|
09/19/2007 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection :* 1) NEED TO POST BOND FOR TEMP POWER 2) FINISH WORK AT SERVICE 3) PLAN CALLS FOR 4/0 TO FFED 200 AMP PANEL 4) PLAN CALLS FOR 350 MCM TO FEET CT CAN. 5) INSTALL PER PLAN OR REVISE DRAWINGS 6) BRACE CONDUCTORS PER INSTRUCTION O DOOR OF CT CAN. 7) RECALL WHEN READY |
|
08/22/2007 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection :* 1. SHEETMETAL SCREWS NOT ALLOWED FOR BONDING 250.8 2. TEMP POWER FOR TEST IS TO TEST EQUIPMENT RIGHT BEFORE FINAL OK CANS IN SOFFIT -- RECEPTIONIST |