Permit: T07CM00904

Parcel: 133243720

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM00904

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/07/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/02/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/28/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
11/07/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELLED
11/06/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. MC CABLES TO BE SUPPORTED AS PER 300.11
2. SUPPORT VDV CABLING AS PER 725.6, 760.6, 800.6, 300.11
3. MANUFACTURES FIXTURE CLIPS TO BE EFFECTIVE
4. GROUND MAKE UP AIR ENCLOSURE NOT JUST DOOR

NOTES: 300.7 - WALKING
210.8(B) KITCHEN
08/07/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. RELOCATE SWITCH LEGS AS DISCUSSED
2. PROVIDE REVISION FOR ALL NEW WORK NOT ON DRAWINGS
3. OK WALLS