Permit: T07CM00894

Parcel: 120081890


Addresses:

126 W OHIO ST #03

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
02/20/2008 BUILDING - FINAL Approved IVRS - Inspection :*
02/05/2008 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
WORK NOT COMPLETE
02/01/2008 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LIGHT FIXTURE UNIT 4 SHIELDED
2) UNIT 3 OK
3) 3 SELF TAPPING SCREWS REQUIRED SINGLE WALL TO DBL WALL CONNECTION B-VENT
01/31/2008 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
01/25/2008 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) NO ANSWER AT NUMBER
2) NO ACCESS 10:46 AM
01/24/2008 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PAINT ROOF ABS VENTS WITH LATEX PAINT
2) 6" MIN. CLEARANCE REQUIRED AT WATER HEATER VENT FROM COMBUSTIBLE
01/22/2008 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
01/18/2008 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ADDRESS ON UNITS
2) PLAN/PERMIT UNIT #2 4" SERVICE PANEL LABELED #3/#4
3) PLAN CALLS FOR 1" H20 LINE SERVICE. YOU HAVE 3/4" DIAMETER
4) EXPOSED OSB ON GABLE END
5) INSPECTED BOTH UNITS ? PLANS SHOW TWO
6) IN NEW SUB PANEL LOOSE MAIN FEEDERS AT POINT OF CONNECTION
7) BUBBLE COVER FOR RECEPT. BELOW #3 SERVICE PANEL
8) PROTECT ROMEX FROM MAIN CONDUIT IN TO HOUSE REAR WALL
9) NEED CLEANOUT FOR KITCHEN SINK
10) MAKE HVAC UNITS FOR CORRECT AMPERAGE, INSTALL BUSHINGS IN KNOCKOUTS HVAC DISCONNECTS, MISSING ROOF JACKS AND PAINT CONDENSATE LINES
11) STOPPED INSPECTION