Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/04/2008 | FRAMING | Approved | IVRS - Inspection :* | |
| 01/31/2008 | FRAMING | Partial Approval | IVRS - Inspection :* 1) PENDING ALL TRADES 2) SECURE B-VENT 3) DRYER VENT MUST BE RIGID HARD PIPE INSIDE WALL 4) OK TO INSULATE |
|
| 01/29/2008 | FRAMING | Partial Approval | IVRS - Inspection :* 1) NEED PROTECTION PLATES ON TPR LINE 2) SIZING OF GAS LINE CALLS FOR 3/4" PIPE ON DRYER AND H20 HEATER-CHANGE OR RED LINE 3) NEED TO SEAL ALL PENETRATIONS ON EXT. LATH 4) MECHANICAL DUCTING NEEDS TO BE EXTENDED TO CONNECT TO EQUIPMENT |
|
| 12/17/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |