Permit: T07CM00850

Parcel: 10408078C


Addresses:

660 W AUTO MALL DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/01/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
04/16/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
TESTED DUCT SMOKE DETECTORS UNITS 1, 3 AND 4
WILL TEST UNIT #2 NEXT PHASE
PROVIDE AIR BALANCE REPORTS
02/20/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PARTS AREA RESTROOMS AND CORRIDOR OK
ON FINAL - SEE BUILDING INSPECTOR FOR TEMP C OF O
10/30/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
OK FOR FINAL PHASE 1
10/24/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
SUPPORT GAS PIPING. 3/8" ID X 36" GAS FLEX NOT ADEQUATE FOR 125,000 BTU
PRE-TEST ALL DUCT SMOKE DETECTORS WITH SMOKE
AIR BALANCE OK PHASE 1
08/14/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
SEE BLDG. INSPECTOR FOR TEMP C OF O FOR PARTS ROOM OFFICES