Permit: T07CM00850

Parcel: 10408078C


Addresses:

660 W AUTO MALL DR


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00850

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/02/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/01/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
ROOF:
1. BOND BUSHING ON DISCONNECTS 250.97
2. PROTECT SEAL TITE FROM SHARP METAL EDGES
04/18/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK TO USE CAFE/PART/CUSTOMER SERVICE AREA,
ROOF INSPECTION TO BE DONE, NEED REVISED PANEL DIRECTORY "INCL"
04/16/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
INSPECTION FOR CUSTOMER CAFE, PARTS/SERVICE AND LOUNGE INTERIOR

1. EMERGENCY LIGHTING NOT PER PLAN
2. PANEL DIRECTORY TO BE CORRECT
3. ROOF TO BE INSPECTED
02/21/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK TCO FOR RESTROOMS, HALLWAY, DRY STORAGE #1 & #2
OK SOFFITS & COLUMNS ROUGH & CAFE CEILING
02/20/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
10/25/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
INSPECTION FOR THE INTERIOR OF SHOWROOM AND OFFICES FOR SHOWROOM ONLY FOR THE PURPOSE OF EMPLOYEE USE
OK INTERIOR OF SHOWROOM AREA OK
08/15/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK OFFICES #39-35
08/14/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS - 314.20
2. WE HAVE MORE THAN 1 NEUTRAL TO A TERMINAL LUG
3. BREAKERS ARE ALSO DOUBLE LUGGED
4. CHECK WORKING CLEARANCES IN MECHANICAL ROOM