Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM00850
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/02/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 04/07/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CUSTOMER SERVICE LOUNGE CEILING TILES |
|
| 04/01/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR CUSTOMER LOUNGE 1. ROLL UP DOOR MOTER REQUIRES DISCONNECTING MEANS NEC 430.109C 2. EMERGENCY LIGHTING NOT FINISHED (OPEN WIRING) 3. NEED STRAP EMT INTO J-BOX 4. CANS TO BE SECURED TO GRID 5. MC TO BE SECURED WITHIN 12" OF TERMINATION CHECK OTHER CORRECTIONS |
|
| 03/11/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SALES/PARTS KITCHEN OK TILES NOTE: DO DEMO, REMOVE TEMP WIRING WILL CHECK NEXT INSPECTION |
|
| 12/12/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 09/18/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING TILES SHOWROOM AREA PENDING LETTER (SEALED) FROM ARCHITECT THAT ALL EXISTING LIGHTING, RACEWAYS, AND CONDUCTORS IN ORIGINAL CEILING WILL BE ABANDONED IN PLACE |
|
| 09/11/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DEMO ALL OLD RACEWAYS, EQUIPMENT, CONDUCTORS ABOVE CEILING 2. SLACK WIRES TO BE SECURED @ BOTH ENDS, DO NOT USE CEILING SUPPORT WIRES 3. EMERGENCY LIGHTING TO BE PER PLAN & NEC 700.12 4. SECURE ALL FIXTURES TO GRID 5. CUT IN EMERGENCY LIGHTS TEST SWITCHES 6. PROVIDE SLACK WIRES FOR ALL FIXTURES |
|
| 08/10/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) HARD LID ABOVE SALE RECEPTION AREA (10 CANS) |
|
| 08/03/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* DEMO OLD LIGHT FIXTURE, FINISH DATA WIRING OK CEILING TILES #39-35 NOTE: - TEMP POWER FOR CONSTRUCTION TO BE GFI PROTECTED RACEWAYS/FEEDERS PROTECTED FROM DAMAGE, COVERS INSTALLED, ETC. |