Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM00850

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/02/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
04/07/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CUSTOMER SERVICE LOUNGE CEILING TILES
04/01/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR CUSTOMER LOUNGE

1. ROLL UP DOOR MOTER REQUIRES DISCONNECTING MEANS
NEC 430.109C
2. EMERGENCY LIGHTING NOT FINISHED (OPEN WIRING)
3. NEED STRAP EMT INTO J-BOX
4. CANS TO BE SECURED TO GRID
5. MC TO BE SECURED WITHIN 12" OF TERMINATION

CHECK OTHER CORRECTIONS
03/11/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
SALES/PARTS KITCHEN OK TILES

NOTE: DO DEMO, REMOVE TEMP WIRING WILL CHECK NEXT INSPECTION
12/12/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
09/18/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING TILES SHOWROOM AREA PENDING LETTER (SEALED) FROM ARCHITECT THAT ALL EXISTING LIGHTING, RACEWAYS, AND CONDUCTORS IN ORIGINAL CEILING WILL BE ABANDONED IN PLACE
09/11/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. DEMO ALL OLD RACEWAYS, EQUIPMENT, CONDUCTORS ABOVE CEILING
2. SLACK WIRES TO BE SECURED @ BOTH ENDS, DO NOT USE CEILING SUPPORT WIRES
3. EMERGENCY LIGHTING TO BE PER PLAN & NEC 700.12
4. SECURE ALL FIXTURES TO GRID
5. CUT IN EMERGENCY LIGHTS TEST SWITCHES
6. PROVIDE SLACK WIRES FOR ALL FIXTURES
08/10/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) HARD LID ABOVE SALE RECEPTION AREA (10 CANS)
08/03/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
DEMO OLD LIGHT FIXTURE, FINISH DATA WIRING
OK CEILING TILES #39-35

NOTE:
- TEMP POWER FOR CONSTRUCTION TO BE GFI PROTECTED
RACEWAYS/FEEDERS PROTECTED FROM DAMAGE, COVERS INSTALLED, ETC.