Permit: T07CM00850

Parcel: 10408078C


Addresses:

660 W AUTO MALL DR


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM00850

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/02/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/01/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/20/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/28/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK PANEL WALL & STORAGE
01/25/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED
01/24/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SUPPORT CONDUITS TO PANEL

OK KITCHEN (EXCEPT PANEL WALL) & BEVERAGE CAFE & LID

* DO NOT COVER WALLS WITHOUT INSPECTIONS
12/12/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL/CEILING CUSTOMER LOUNGE
AREA BATHROOMS - ELIGHTS TO BE CUT IN (TEST SWITCH)
08/09/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS N.E OFFICE SALES AREA
08/02/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS SALES MANAGER AND SALES TOWER
07/31/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PROTECT M/C CABLE IN CHANNELS 330.17
ALSO, AT STUDS
2. PROTECT PVC IN CHANNELS
3. PLANS CALL FOR CONDUCTORS IN RACEWAY (3) 3.2(C)
PLEASE VERIFY USAGE OF M/C CABLE
4. PLEASE VERIFY IF PVC IS ALLOWED IN WALLS
PLANS CALL FOR EMT 3.2(G)
5. SECURE VDV CABLE IN WALL AT BOXES
07/25/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ELECTRICAL WALL COVER SHOWROOM OFFICES
#6, 8, 10, 11, 12, 7, 9, 13, 14, 15 -- AFTER NAIL PLATES ARE INSTALLED ALONG BACK WALL -- NEC 330.17
AND 4 OFFICES S.E SHOWROOM (WALLS)

OK FLOOR RECEPTACLES
WORK STATIONS #7 ON PLAN
07/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ELECTRICAL
OK WALL COVER ROOMS #39-#35