Permit: T07CM00844

Parcel: 129011130


Addresses:

1010 S PLUMER AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/19/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/17/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ALL RECEPTS IN WORKING AREAS MUST BE GFI PROTECTED
PER 511.12 NEC
2. ARCING TYPE EQUIP. SUCH AS WELDERS, METERS, SWITCHES, ETC. MUST BE RATED FOR USE IN 511 AREAS
PER NEC, ALL REQUIREMENTS OF 511 NEC WILL APPLY.
3. OBTAIN THE SERVICES OF A REGISTERED ARCH. TO OBTAIN PLANS AND CLASSIFY BUILDING FOR USE OF A REPAIR FACILITY FOR AUTOMOTIVE USE. PLANS ON SITE ONLY REFLECT EXISTING CONDITIONS.