Permit: T07CM00837

Parcel: 30503004B

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T07CM00837

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/26/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
10/15/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
UNISEX B CLOSET FLANGE OK
10/11/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. UNISEX RESTROOM NORTH SIDE OF DORMITORY IN WALL OK
2. CALL BACK FOR CLOSET FLANGE INSPECTION
08/21/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
08/20/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) MENS TOILET A WASTE AND VENT AND WATER PIPING OK
08/17/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
TOILET A MENS RESTROOM, LAV DRAIN ARM REQUIRED TO BE APPROVED 1 1/2 DRAINAGE MATERIAL, 2" DRAIN ARM REQUIRES 2" P-TRAP, 2" P-TRAP CANNOT BE USED ON 1 1/4" TAILPIECE DEVICE.
07/10/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
ROOM #1 OK FOR PLUMBING FINAL
ROOM #14 OK WASTE & VENT & WATER PIPING
06/21/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WATER TEST LAV SOUTHEAST ROOM 1 OK
CLOSET FLANGE OK

1. PROVIDE SUPPORTS FOR RE-ROUTE OF CONDENSATE DRAIN
06/15/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) WATER PIPING TO NEW LAV LOCATION SOUTH EAST DORM AND CAPS FOR WATER AT OLD LOCATION OK
2) STOOL SHAL HAVE CLOSET FLANGE INSPECTION PRIOR TO SETTING STOOL
3) CONDENSATE TO BE TERMINATED TO NEW LAV
4) WATER TEST LAV DRAINAGE AND VENT-SHALL CAP OLD LAV DRAIN